A consumer’s overhead service conductors are to be routed below the bottom edge of a second story window. What requirement must be met?
  1. Service conductors must always be routed above windows.
  2. The service conductors must be SOW or TECK90 near windows.
  3. 1 m of clearance must be maintained between windows and the service conductors.
  4. There are no requirements for service conductors near windows as long as the minimum height to finished grade level is satisfied.
Explanation
Answer: C. Explanation: CEC 2021 6-112 4) States that exposed service conductors or cables that are not higher than windows, doors, and porches shall have a clearance of not less than 1 m from the windows, doors, or porches.